Page 1 of 2 A summary of past postings from the Beowulf mailing list up to October 10, 2003
In the fall of 2003, there was something of a general theme on the Beowulf mailing list. The theme revolved around the environment in which our clusters live. That is, the machine room. This topic involves the design of machine
rooms and how to save our dear clusters from imminent disaster when
the cooling fails. Join us as we take a look at killing power (quickly), building machine rooms, and environment monitoring.
Beowulf: Kill the Power Faster than poweroff?
On the 11th of September 2003 David Mathog asked about ways to shut down
a system and kill the power faster than using the poweroff command.
He was interested in ways to shut down systems in emergency over
heating conditions. He has some Athlon systems that he wanted to
shutdown in the event of a cooling fan failure. The ensuing
discussion was very interesting because not only was a fast shut
down of the system discussed but also some old Unix habits.
Initially, David mentioned he wanted something like running a
sync command and then powering off the system. The sync command
would flush the file system buffers and get a consistent file system
state, hopefully completely flushing the journal for a journaled
file system. The first suggestion from Ariel Sabiguero was to do
either use the halt -p -f command or poweroff -f. He said that
in his tests it only took 3 seconds to shuts down his system instead
of 20 seconds. David responded that this approach did indeed work
quickly, but was not a clean shutdown, forcing the file system to
be repaired via fsck upon reboot including fixing inodes. He
didn't necessarily mind this since, in his opinion, a fsck is better
than fried hardware. Bernd Schubert added that since it was a
2.4.21 kernel or later, that a series of changes to
/proc/sysrq-trigger would force a shutdown in less than a second
on his machine.
At his point the discussion brought in the question of how to sync the
file system prior to shutdown. Alan Grossfield mentioned the ever
popular system administrator approach of running the sync command
3 times before shutting down. Donald Becker and others said that this
sysadmin habit was before the advent of good journaling file systems.
Now, just one sync should be sufficient to ensure a consistent
file system before shutting down. Who says you can't teach an old
sysadmin new tricks?
The final piece of the discussion was how Linux unmounted file systems
during the shutdown. The esteemed Robert Brown (Bob or rgb to people
on the list) started off the discussion by mentioning that applications
that have an open file(s) would have to be killed quickly to avoid a
race and to satisfy David's initial request for a very fast shutdown.
Greg Lindahl provided some great insight into how Linux shuts down. He
pointed out that Linux nicely kills the processes during shutdown. He
also mentioned that if you want to do it faster, using the kill -9
command will greatly speed things along. Robert Brown also added that
during a fast shut down you might get some of the
infamous .nfs20800200 leftover files if the system had an active
nfs mount.
The moral of these discussions is that if you have to do a very fast
shutdown, you should first make sure you are using a journaling
file system on all disks on the system in question, and the follow
one of the suggested methods to shut down the system. However, you
could end up having to fsck the file systems. The final moral is
that you don't need to run sync three times before having to
shutdown a system.
Beowulf Q: Building a small machine room? Materials/costs/etc.
There was a very interesting discussion about designing machines rooms
for clusters that was initiated by Brian Dobbins on the 16th of
September 2003. He wanted to solicit the advice of people who had experience
designing small machine rooms for their clusters. Of course the first
reply was from Robert Brown, who has lately taken machine room requirements,
especially electrical, to heart. He responded with many good comments
about power, airflow, structural integrity (primarily weight), sound
and light, networking, security, comfort an convenience. Michael Stein
and Bob Brown added many more details to the electrical requirements for
supplying power to the room including estimating the power required,
what kind of room power supplies to use, and where to put the power
distribution panels. Bob went on to add additional items such as a
thermal kill switch for the machine room in the even of a complete
cooling failure. He pointed out that in the event of a room cooling
failure, the temperature can go from a reasonable temperature to system
thermal failure in just a few minutes (it's better to spend some time
fixing file systems than to have to purchase all new equipment). He also
extended his comments about a raised floor for the machine room. Bob also
made a very good point that it is highly recommended to get facilities
people involved very early in the design process not only for the design
of the room but also operational issues such as not shutting down the
chillers in the winter just because it's cold outside!
|